PEC Questions Part 1

PEC Questions Part 1

University

84 Qs

quiz-placeholder

Similar activities

Pharmacological and Parenteral Therapies

Pharmacological and Parenteral Therapies

University

86 Qs

SP24 SIG DIGIT PRACTICE

SP24 SIG DIGIT PRACTICE

University

80 Qs

Eyelids

Eyelids

University

84 Qs

Med Surg Unit 1-5 Review Questions (#1)

Med Surg Unit 1-5 Review Questions (#1)

University

89 Qs

Fisiologia renal 1era parte

Fisiologia renal 1era parte

University

89 Qs

MAP - Strand 11 - Cardiovascular System

MAP - Strand 11 - Cardiovascular System

9th Grade - University

80 Qs

EKim Science7 Unit2.1 Climate'sEffect SG

EKim Science7 Unit2.1 Climate'sEffect SG

7th Grade - University

82 Qs

Sound Energy Quiz Review

Sound Energy Quiz Review

8th Grade - University

89 Qs

PEC Questions Part 1

PEC Questions Part 1

Assessment

Quiz

Science

University

Medium

Created by

Reggie Tano

Used 22+ times

FREE Resource

84 questions

Show all answers

1.

MULTIPLE CHOICE QUESTION

1 min • 1 pt

Which of the following wires is not suitable tor both dry and wet locations?

THHW

RH

XHHW

TW

2.

MULTIPLE CHOICE QUESTION

1 min • 1 pt

The equipment grounding conductor of a branch circuit shall be identified by a continuous

color.

green

black

white

yellow

3.

MULTIPLE CHOICE QUESTION

1 min • 1 pt

Which of the following colors of insulation or mark;ng are permitted to identify "hot" phase conductors·

in conduit wiring methods?

Black, red, and blue for 120/208-volt systems

Yellow, orange, and brown for 277/480-volt systems

Any colors except white, gray, or green

AII of the above

4.

MULTIPLE CHOICE QUESTION

1 min • 1 pt

A copper THHN feeder conductor consists of 40 amperes of continuous load and 35 amperes of non-

continuous load, and supplies a load that does not contain any general use receptacles but has three

current-carrying conductors in a raceway-with terminations rated at 75 degrees C. This means that the

minimum standard overcurrent device required for the feeder is which of the following:

70 amps

76 amps

86 amps

90 amps

5.

MULTIPLE CHOICE QUESTION

1 min • 1 pt

For a 30 amp receptacle connected to a 30 am~ branch circuit supplying two or more outlets, the

total cord-and-plug load may not exceed which of the following sizes:

24 amps

16 amps

15 amps

12 amps

6.

MULTIPLE CHOICE QUESTION

1 min • 1 pt

The ampacity of a conductor must be derated where the ambient temperature exceeds which of the

following:

30 degrees C

32 degrees C

26 degrees C

20 degrees C

7.

MULTIPLE CHOICE QUESTION

1 min • 1 pt

Disregarding any exceptions, a conductor rated 56 amperes shall be protected by a fuse sized at

which of the following:·

60 amp

50 amp·

30 amp

20 amp