PEC Questions Part 1

PEC Questions Part 1

University

84 Qs

quiz-placeholder

Similar activities

Pharm 2 Exam 1 Review

Pharm 2 Exam 1 Review

University

82 Qs

Exam 1 A & P

Exam 1 A & P

University

89 Qs

Chapters 8 & 9 Review

Chapters 8 & 9 Review

12th Grade - University

80 Qs

Intro to Soils Exam 2 (3-4)

Intro to Soils Exam 2 (3-4)

University

80 Qs

Ovarian Structure and Function Quiz

Ovarian Structure and Function Quiz

University

82 Qs

EARTH'S SPHERES AND LAYERS

EARTH'S SPHERES AND LAYERS

6th Grade - University

80 Qs

A&P 1 2113 - Chapter 4/5 Review

A&P 1 2113 - Chapter 4/5 Review

University

89 Qs

بنك د/محمد شحاته

بنك د/محمد شحاته

University

83 Qs

PEC Questions Part 1

PEC Questions Part 1

Assessment

Quiz

Science

University

Medium

Created by

Reggie Tano

Used 22+ times

FREE Resource

84 questions

Show all answers

1.

MULTIPLE CHOICE QUESTION

1 min • 1 pt

Which of the following wires is not suitable tor both dry and wet locations?

THHW

RH

XHHW

TW

2.

MULTIPLE CHOICE QUESTION

1 min • 1 pt

The equipment grounding conductor of a branch circuit shall be identified by a continuous

color.

green

black

white

yellow

3.

MULTIPLE CHOICE QUESTION

1 min • 1 pt

Which of the following colors of insulation or mark;ng are permitted to identify "hot" phase conductors·

in conduit wiring methods?

Black, red, and blue for 120/208-volt systems

Yellow, orange, and brown for 277/480-volt systems

Any colors except white, gray, or green

AII of the above

4.

MULTIPLE CHOICE QUESTION

1 min • 1 pt

A copper THHN feeder conductor consists of 40 amperes of continuous load and 35 amperes of non-

continuous load, and supplies a load that does not contain any general use receptacles but has three

current-carrying conductors in a raceway-with terminations rated at 75 degrees C. This means that the

minimum standard overcurrent device required for the feeder is which of the following:

70 amps

76 amps

86 amps

90 amps

5.

MULTIPLE CHOICE QUESTION

1 min • 1 pt

For a 30 amp receptacle connected to a 30 am~ branch circuit supplying two or more outlets, the

total cord-and-plug load may not exceed which of the following sizes:

24 amps

16 amps

15 amps

12 amps

6.

MULTIPLE CHOICE QUESTION

1 min • 1 pt

The ampacity of a conductor must be derated where the ambient temperature exceeds which of the

following:

30 degrees C

32 degrees C

26 degrees C

20 degrees C

7.

MULTIPLE CHOICE QUESTION

1 min • 1 pt

Disregarding any exceptions, a conductor rated 56 amperes shall be protected by a fuse sized at

which of the following:·

60 amp

50 amp·

30 amp

20 amp