1.

MULTIPLE CHOICE QUESTION

30 sec • 1 pt

A small residential duplex has a 3kW counter mounted cooktop and a 4kW wall mounted oven installed in each unit. Determine the demand load in kW, to be added to the ungrounded service entrance conductors for the cooking equipment.

9.7 kW

14 kW

11.2 kW

10.5kW

2.

MULTIPLE CHOICE QUESTION

30 sec • 1 pt

What is the demand load in kW, for the branch circuit condcutors supplying an 8kW residential electric range.

8.0 kW

6.4 kW

6.0 kW

7.2 kW

3.

MULTIPLE CHOICE QUESTION

30 sec • 1 pt

An eight-unit multifamily dwelling is to have the following electric clothes dryers installed in and in the laundry room of the tenants.

Two – 4.5 kW rated

Two – 5.5 kW rated

Two – 6.0 kW rated

Two – 6.5 kW rated.

27 kW

27.6kW

34.5kW

33.8kW

4.

MULTIPLE CHOICE QUESTION

30 sec • 1 pt

A one family dwelling unit is to have the following fastened in place appliances installed

One - 1200 VA dishwasher

One - 4,000 VA Water heater

One - 1,150 VA garbage disposal

One – 700 VA attic fan

One – 1920 VA garage door opener

7728VA

6728VA

6276VA

8970VA

Tags

NGSS.HS-PS3-1

5.

MULTIPLE CHOICE QUESTION

30 sec • 1 pt

A ten (10) unit apartment complex is to have a 10kW electric range installed in each unit. When sizing the ungrounded service-entrance conductors, the total demand load for the multiple ranges is

30 kW

80 kW

25 kW

100 kW

6.

MULTIPLE CHOICE QUESTION

30 sec • 1 pt

What is the branch circuit demand load in amperes, for one 16kW, 240V single phase residential electric range

33A

50A

40A

67A

7.

MULTIPLE CHOICE QUESTION

30 sec • 1 pt

Determine the demand load in kW, to be added to the ungrounded service-entrance conductors for a 9.6 kW residential electric range.

9.6 kW

8.0 kW

10.0 kW

12.0 kW

Access all questions and much more by creating a free account

Create resources

Host any resource

Get auto-graded reports

Google

Continue with Google

Email

Continue with Email

Classlink

Continue with Classlink

Clever

Continue with Clever

or continue with

Microsoft

Microsoft

Apple

Apple

Others

Others

Already have an account?