Sprayed Applied Fireproofing 4a

Sprayed Applied Fireproofing 4a

Professional Development

7 Qs

quiz-placeholder

Similar activities

KYC2KYC- A20 vs A5s / A10 vs Y91

KYC2KYC- A20 vs A5s / A10 vs Y91

Professional Development

10 Qs

Steel part 3 slide 1-25 set 2

Steel part 3 slide 1-25 set 2

Professional Development

8 Qs

Teknik Pengukuran (Pre Test)

Teknik Pengukuran (Pre Test)

Professional Development

10 Qs

Pelaksanaan Kurikulum Tahun 2021

Pelaksanaan Kurikulum Tahun 2021

Professional Development

9 Qs

Quality Control Measures in Asphalt Pavement Construction

Quality Control Measures in Asphalt Pavement Construction

Professional Development

10 Qs

MAG 3

MAG 3

Professional Development

6 Qs

IBS as Sustainable Construction in Malaysia

IBS as Sustainable Construction in Malaysia

Professional Development

10 Qs

ASME V short quiz

ASME V short quiz

Professional Development

5 Qs

Sprayed Applied Fireproofing 4a

Sprayed Applied Fireproofing 4a

Assessment

Quiz

Professional Development

Professional Development

Easy

Created by

Piledriverob Piledriverob2375

Used 10+ times

FREE Resource

7 questions

Show all answers

1.

MULTIPLE CHOICE QUESTION

30 sec • 1 pt

If there were 76 BEAMS to receive fireproofing on the 2nd floor of building, how many should be checked for THICKNESS

19 BEAMS

15 beams

all the beams

Answer explanation

Media Image

IBC

1705.15.4.5 STRUCTURAL MEMBERS

...............Thickness testing shall be performed on not less than 25 percent of the Structural members on each floor...

2.

MULTIPLE CHOICE QUESTION

30 sec • 1 pt

When determining the Thickness of a DENSITY test specimen , how many measurements are made per sample ?

12*

9

7

Answer explanation

Media Image

12A

5.4.4.2 THICKNESS

.......................A minimum of 12 measurements shall be made in a symmetrical pattern prior to removal. The average value of these 12 measurement shall be deemed the thickness of the specimen

3.

MULTIPLE CHOICE QUESTION

30 sec • 1 pt

According to manual 12A , what is the minimum size of a DENSITY sample ?

48

sq. in.

60 inches

100 inches

Answer explanation

Media Image

12A

5.4.4 MEASUREMENT Method

5.4.4.1 Length & Width

..............................................

The specimen area shall be not less than 48 sq. in. where possible , no dimension shall be less than 3 in.

4.

MULTIPLE CHOICE QUESTION

30 sec • 1 pt

How many individual Thickness measurements ( total ) need to be taken for a wide flanged COLUMN ?

24*

12

9

Answer explanation

Media Image

IBC

1705.15.4.8

WIDE FLANGED COLUMN

At wide flanged column, thickness measurements shall be made at 12 locations around column at each end of a 12-inch length

5.

MULTIPLE CHOICE QUESTION

30 sec • 1 pt

How many DENSITY samples should be obtained for a floor with 12,300 ft2 of floor area & the columns, beams & underside of decks receiving fireproofing ?

15*

10

20

Answer explanation

Media Image

IBC

1705.15.5 DENSITY

  1. 1.

  2. From each Floor , Roof , & Wall assembly at the rate of not less than ONE Sample for every 2,500 square feet

2.

From Beams , Girders , Trusses , & Columns at the rate of not less than ONE Sample for each type of Structural member for each 2,500 square feet

6.

MULTIPLE CHOICE QUESTION

30 sec • 1 pt

If the specified Thickness for a Beam is 7/8 inches , what is the minimum allowable individual measurement ?

21/32nd

3/4

5/8

Answer explanation

Media Image

IBC

1705.15.4.1

MINIMUM ALLOWABLE THICKNESS

.............For design thickness of less than 1 inch. the minimum allowable individual thickness shall be design the design thickness minus

25 percent

7.

MULTIPLE CHOICE QUESTION

30 sec • 1 pt

A.H.S.S column requires a specified thickness of 1-1/4 inches, four measurements are taken as follows

1-1/4 , 1-1/8 , 1-7/16 , 1-1/2

1 - 9/32nd in.

1 - 1/4

1 - 5/16

Answer explanation

Media Image

Discover more resources for Professional Development