Gas Installation Ventilation Requirements

Gas Installation Ventilation Requirements

Assessment

Flashcard

Other

Professional Development

Hard

Created by

Eugene Schutte

FREE Resource

Student preview

quiz-placeholder

15 questions

Show all answers

1.

FLASHCARD QUESTION

Front

Gas installations that do not need purpose provided ventilation.

Back

An instantaneous flueless water heater fitted in a kitchen between 5 m³ and 10 m³ volume.

2.

FLASHCARD QUESTION

Front

Minimum ventilation requirement for an open flued boiler with a 30 kW (net) input.

Back

150 cm²

3.

FLASHCARD QUESTION

Front

Ventilation requirement for a room sealed boiler with a 27 kW (net) input, vented direct to outside.

Back

High Level: 135 cm², Low Level: 270 cm²

4.

FLASHCARD QUESTION

Front

Minimum ventilation for a flueless natural gas space heater with 1.7 kW (net) input in a 60 m³ room.

Back

8.5 cm² + openable window

5.

FLASHCARD QUESTION

Front

Ventilation requirement for a flueless instantaneous water heater with 10.5 kW (net) input in a laundry.

Back

52.5 cm² plus an openable window

6.

FLASHCARD QUESTION

Front

Gas fire below 7 kW (net) rated heat input fitted in a room.

Back

Does not need purpose provided ventilation.

7.

FLASHCARD QUESTION

Front

Natural draught room sealed boiler fitted within a compartment.

Back

Needs purpose provided ventilation.

Create a free account and access millions of resources

Create resources

Host any resource

Get auto-graded reports

Google

Continue with Google

Email

Continue with Email

Classlink

Continue with Classlink

Clever

Continue with Clever

or continue with

Microsoft

Microsoft

Apple

Apple

Others

Others

By signing up, you agree to our Terms of Service & Privacy Policy

Already have an account?