Gas Installations and Ventilation Requirements
Flashcard
•
Other
•
Professional Development
•
Practice Problem
•
Hard
Eugene Schutte
FREE Resource
Student preview

15 questions
Show all answers
1.
FLASHCARD QUESTION
Front
Gas installations not needing purpose provided ventilation
Back
An instantaneous flueless water heater fitted in a kitchen between 5 m³ and 10 m³ volume
2.
FLASHCARD QUESTION
Front
Minimum ventilation for 30 kW open flued boiler in a room
Back
150 cm²
3.
FLASHCARD QUESTION
Front
Ventilation requirement for 27 kW room sealed boiler vented outside
Back
135 cm² high level, 270 cm² low level
4.
FLASHCARD QUESTION
Front
Minimum ventilation for 1.7 kW flueless natural gas heater in 60 m³ room
Back
8.5 cm² + openable window
5.
FLASHCARD QUESTION
Front
Ventilation for 10.5 kW flueless water heater in laundry
Back
52.5 cm² plus an openable window
6.
FLASHCARD QUESTION
Front
Gas fire below 7 kW in a room
Back
Does not need purpose provided ventilation
7.
FLASHCARD QUESTION
Front
Natural draught room sealed boiler in a compartment
Back
Needs purpose provided ventilation